Special Wire and Cable > Oil-Resistant Cable
XHHW-2 Non-Shielded Petroleum Cable
Suitable for installation in conduit and on supported overhead systems, this XHHW-2 petroleum cable is also rated for direct burial, wet or dry locations, and outdoor light-protected raceways.
Built with flame-retardant XLPE insulation compliant with UL 44 XHHW-2 requirements and ICEA S-95-658, and protected by a special flame-retardant PVC outer jacket rated per UL 1277, the cable is engineered for oil field, tray and conduit power and control applications requiring hydrocarbon resistance.





Key Features
Flame-Retardant XLPE Insulation
Insulation complies with UL 44 XHHW-2 requirements and ICEA S-95-658, with 14AWG-10AWG sizes additionally meeting VW-1 flame test.
Hydrocarbon Resistance
Special outer jacket resists aliphatic and aromatic hydrocarbons, suited to oil field and petroleum-adjacent installations.
Sunlight & Moisture Resistant
UL 1277 compliant special PVC jacket provides flame-retardant, sunlight and moisture resistant performance for outdoor exposure.
90°C Conductor Rating
Rated for continuous conductor operation up to 90°C, with an operating temperature range of -20°C to 90°C.
Versatile Installation
Suitable for conduit, supported overhead systems, cable tray, direct burial, and wet or dry locations.
Dual CE & UL Certification
Certified to both European CE and North American UL standards, meeting ICEA S-73-532, UL 1277 and UL 83.
OEM & ODM Capabilities
3-Core & 4-Core Options
Available as 3-core (power cable configuration) or 4-core (control cable configuration with 1 ground core).
Custom Conductor Sizing
Available from 14 AWG up to 500 KCMIL to match your power and control circuit requirements.
Ground Wire Sizing per Circuit
Ground conductor AWG size matched to each conductor size per the dimensional data table for correct circuit protection.
Custom Jacket Options
Standard black special PVC jacket; alternative colors and additional UV protection levels available on request.
Custom Length & Reel Packaging
Supplied in custom cut lengths and reel/coil packaging configurations to suit project logistics needs.
Private Labeling & Branding
OEM/ODM packaging, reel labeling and documentation support available for distributors and oilfield contractors.
Technical Specifications
| Conductor | Annealed bare copper, per ASTM B3 & B8; 4-core: control cable, 3-core: power cable, 1 core: ground wire |
|---|---|
| Ground Wire | Sized per conductor per dimensional data table |
| Insulation | Flame-retardant XLPE per UL 44 XHHW-2 & ICEA S-95-658; 14AWG–10AWG also VW-1 compliant |
| Inner Layer | Binder tape |
| Shield | None (non-shielded construction) |
| Drain Wire | None |
| Ripcord | None |
| Outer Jacket | Special PVC, flame-retardant, sunlight & moisture resistant, per UL 1277, black |
| Rated Voltage | 600V |
| Flame-Retardant Standard | IEC 60332-3-22 |
| Operating Temperature Range | -20°C ~ 90°C |
| Max Conductor Operating Temperature | 90°C |
| Color Coding | Per ANSI, IEC, JIS |
| Chemical Resistance | Aliphatic and aromatic hydrocarbons |
| Standard | ICEA S-73-532; UL 1277; UL 83 |
| Certification | Dual certified: EU CE, North America UL |
| Rated Voltage | 600V |
|---|---|
| Max Temperature | 90°C |
| Certification | CE + UL |
| Conductor Range | 14 AWG – 500 KCMIL |
| Conductor Size (AWG/KCMIL) | Ground Wire (AWG) | Insulation Thickness – PVC (mm) | Insulation Thickness – Nylon (mm) | Jacket Thickness (mm) | Outer Diameter (mm) | Weight (kg/km) | Ampacity (Amps) |
|---|---|---|---|---|---|---|---|
| 14 | 14 | 0.38 | 0.10 | 1.14 | 9.25 | 135 | 25 |
| 12 | 12 | 0.38 | 0.10 | 1.14 | 10.36 | 188 | 30 |
| 10 | 10 | 0.51 | 0.10 | 1.14 | 11.66 | 284 | 40 |
| 8 | 10 | 0.76 | 0.13 | 1.52 | 15.49 | 449 | 55 |
| 6 | 8 | 0.76 | 0.13 | 1.52 | 18.42 | 628 | 75 |
| 4 | 8 | 1.02 | 0.15 | 2.03 | 21.77 | 963 | 95 |
| 2 | 6 | 1.02 | 0.15 | 2.03 | 25.30 | 1433 | 130 |
| 1 | 6 | 1.27 | 0.18 | 2.03 | 28.14 | 1720 | 150 |
| 1/0 | 6 | 1.27 | 0.18 | 2.03 | 30.66 | 2159 | 170 |
| 2/0 | 6 | 1.27 | 0.18 | 2.03 | 32.94 | 2586 | 195 |
| 3/0 | 4 | 1.27 | 0.18 | 2.03 | 35.81 | 3158 | 225 |
| 4/0 | 4 | 1.27 | 0.18 | 2.03 | 38.86 | 3834 | 260 |
| 250 | 4 | 1.52 | 0.20 | 2.79 | 42.09 | 4508 | 290 |
| 350 | 3 | 1.52 | 0.20 | 2.79 | 49.81 | 6469 | 350 |
| 500 | 2 | 1.52 | 0.20 | 2.79 | 56.74 | 8660 | 430 |
| Conductor Size (AWG/KCMIL) | Ground Wire (AWG) | Insulation Thickness – PVC (mm) | Insulation Thickness – Nylon (mm) | Jacket Thickness (mm) | Outer Diameter (mm) | Weight (kg/km) | Ampacity – Rating A (Amps) | Ampacity – Rating B (Amps) |
|---|---|---|---|---|---|---|---|---|
| 8 | 10 | 0.76 | 0.13 | 1.52 | 17.22 | 561 | 44 | 55 |
| 6 | 8 | 0.76 | 0.13 | 1.52 | 19.81 | 813 | 60 | 75 |
| 4 | 8 | 1.02 | 0.15 | 2.03 | 23.93 | 1222 | 76 | 95 |
| 2 | 6 | 1.02 | 0.15 | 2.03 | 27.56 | 1823 | 104 | 130 |
| 1 | 6 | 1.27 | 0.18 | 2.03 | 31.67 | 2261 | 120 | 150 |
| 1/0 | 6 | 1.27 | 0.18 | 2.03 | 33.38 | 2695 | 136 | 170 |
| 2/0 | 6 | 1.27 | 0.18 | 2.03 | 36.88 | 3405 | 156 | 195 |
| 3/0 | 4 | 1.27 | 0.18 | 2.03 | 40.00 | 4101 | 180 | 225 |
| 4/0 | 4 | 1.27 | 0.18 | 2.03 | 44.91 | 5115 | 208 | 260 |
| 250 | 4 | 1.52 | 0.20 | 2.79 | 49.20 | 6021 | 232 | 290 |
| 350 | 3 | 1.52 | 0.20 | 2.79 | 55.37 | 8155 | 280 | 350 |
| 500 | 2 | 1.52 | 0.20 | 2.79 | 63.35 | 11271 | 344 | 430 |
Construction & Configuration
Conductor
Annealed bare copper conductor per ASTM B3 & B8; 4-core configured as a control cable, 3-core as a power cable, with 1 core reserved as ground wire.
Insulation
Flame-retardant XLPE insulation compliant with UL 44 XHHW-2 requirements and ICEA S-95-658; 14AWG-10AWG sizes additionally meet VW-1 flame testing.
Inner Layer
Binder tape holds the conductor bundle together; construction is non-shielded, without drain wire or ripcord.
Outer Jacket
Special black PVC jacket, flame-retardant, sunlight and moisture resistant, compliant with UL 1277.
Voltage & Thermal Rating
Rated 600V with continuous conductor operation up to 90°C and an operating range of -20°C to 90°C.
Core & Size Configuration
Available in 3-core and 4-core configurations from 14 AWG to 500 KCMIL, per the dimensional data tables above.
Standards & Test Documentation
ICEA S-73-532 / UL 1277 / UL 83
Cable construction complies with ICEA S-73-532, UL 1277 tray cable requirements and UL 83 thermoplastic-insulated wire standards.
UL 44 XHHW-2 / ICEA S-95-658
Flame-retardant XLPE insulation meets UL 44 XHHW-2 requirements and ICEA S-95-658 XLPE insulation specifications.
Dual CE & UL Certified
Certified to both European CE and North American UL standards, alongside IEC 60332-3-22 flame-retardant compliance.
Need XHHW-2 Petroleum Cable?
Send us your required core count, conductor size and jacket specification. Our team will review your requirements and prepare a quotation.