Special Wire and Cable > Fire-Resistant Cable
FFX-CAT3FTPXP22FR Fire-Resistant CAT3 FTP Data Cable
Designed as a circuit-integrity fire alarm wiring cable compatible with all leading connection systems complying with EN 50173, this CAT3 FTP shielded data cable is engineered per IEC 61156 and BS EN 50288 system requirements.
Available in 1, 2 or 4-pair configurations with an overall aluminum/polyester tape screen and tinned copper drain wire, the cable continues transmitting data even when directly exposed to fire, while offering reliable data transmission and circuit integrity performance. It also complies with BS 5839:2002 test clause requirements.





Key Features
Circuit Integrity Under Fire
Continues transmitting data when directly exposed to fire, complying with IEC 60331-21, BS 6387 CWZ and BS 5839:2002 test requirements.
Overall Foil Screen
Aluminum/polyester tape overall screen with tinned copper drain wire provides EMC protection beyond unshielded UTP constructions.
Low Smoke Zero Halogen
LSZH sheath per BS 7652 §6.1 / BS 7655 §2.6 LTS3 class, with low halogen and corrosive gas emission for occupied buildings.
EN 50173 Compatible
Compatible with all leading structured cabling connection systems complying with EN 50173, IEC 61156 and BS EN 50288.
High Insulation Resistance
Insulation resistance ≥1000MΩ×km at 20°C, supporting reliable long-distance signal integrity.
OEM & ODM Capabilities
1/2/4-Pair Options
Available as FFX-CAT3FTP1P22FR, FFX-CAT3FTP2P22FR or FFX-CAT3FTP4P22FR to match your circuit count requirements.
Choice of Jacket Color
Available in red, white or black outer jacket to support circuit identification and fire alarm color-coding conventions.
Multi-Standard Compliance Support
Engineering support to align cable selection with country-specific fire, smoke and toxicity standards for your project.
Bundled Multi-Cable Configuration
Cables can be assembled into bundles of 8 pairs or more, and further grouped into larger multi-bundle assemblies for large installations.
Custom Length & Reel Packaging
Supplied in custom cut lengths and reel/coil packaging configurations to suit project logistics needs.
Private Labeling & Branding
OEM/ODM packaging, reel labeling and documentation support available for distributors and fire system contractors.
Technical Specifications
| Conductor | Plain annealed copper wire, stranded, per IEC(EN) 60228 class 2 |
|---|---|
| Insulation | Polyethylene with fire-resistant silicone rubber E12 class, per BS 7655 §1.1 |
| Pair Twisting | Different lay lengths per pair to minimize crosstalk; 4 cores per twisted-pair group |
| Cabling | Pairs assembled together; groups of 8+ pairs bundled, then multiple bundles assembled together |
| Overall Screen | Aluminum/polyester tape with tinned copper drain wire |
| Fire Barrier Layer | None |
| Armour | None |
| Outer Sheath | Thermoplastic per BS 7652 §6.1 / BS 7655 §2.6, LSZH compound LTS3 class (SW2-SW4 type) |
| Jacket Color | Red, white or black (customer choice) |
| Working Voltage | 60V |
| Design Standard | BS 7629-1 / EN 50173 |
| Insulation Resistance | ≥1000MΩ×km at 20°C |
| Short-Circuit Temperature | 50°C |
| Operating Temperature (Fixed) | -5°C ~ +50°C |
| Installation Temperature | -20°C ~ +90°C |
| Min. Bending Radius | 8 × OD |
| Working Voltage | 60V |
|---|---|
| Insulation Resistance | ≥1000MΩ×km |
| Min. Bend Radius | 8 × OD |
| Frequency (MHz) | NEXT (dB/100m) Min/Typ/Standard | Insertion Loss – IL (dB/100m) | Structural Return Loss – SRL (dB/100m) Min/Typ/Standard |
|---|---|---|---|
| 1 | 43.0/48.0/41.0 | 2.6 | 13.0/16.0/12.0 |
| 4 | 34.0/38.0/32.0 | 5.6 | 13.0/16.0/12.0 |
| 8 | 29.0/33.0/26.0 | 8.5 | 13.0/16.0/12.0 |
| 10 | 28.0/33.0/26.0 | 9.8 | 13.0/16.0/12.0 |
| 16 | 25.0/30.0/23.0 | 13.1 | 11.0/14.0/10.0 |
| Cable Code | No. of Pairs | Insulation Thickness (mm) | Nominal Diameter (mm) | Nominal Weight (kg/km) |
|---|---|---|---|---|
| FFX-CAT3FTP1P22FR | 1 | 0.25 | 6.8 | 48 |
| FFX-CAT3FTP2P22FR | 2 | 0.25 | 8.1 | 97 |
| FFX-CAT3FTP4P22FR | 4 | 0.25 | 10.4 | 122 |
Construction & Configuration
Conductor
Plain annealed copper wire, stranded, complying with IEC(EN) 60228 class 2.
Insulation & Pair Twisting
Fire-resistant silicone rubber E12 class insulated polyethylene, twisted with varying lay lengths per pair to minimize crosstalk.
Overall Screen
Aluminum/polyester tape overall screen with a tinned copper drain wire for EMC protection (FTP construction).
Fire Barrier & Armour
No dedicated fire barrier layer or armour — fire performance is achieved through insulation and sheath material selection.
Outer Sheath
LSZH thermoplastic sheath per BS 7652 §6.1 / BS 7655 §2.6, available in red, white or black.
Pair Count Configuration
Available in 1, 2 or 4-pair versions (FFX-CAT3FTP1P22FR / 2P22FR / 4P22FR), per the dimensional data table above.
Standards & Test Documentation
Fire Circuit Integrity Standards
IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814 (FE180); BS 8434-2 (120mins); BS 5839-1 Clause 26.2e; CEI 20-36/2-1; SS 229-1; NBN C 30-004 (cat. F3); NF C32-070-2.3 (CR1). Mechanical shock integrity: EN 50200 (PH120), CEI 20-36/4-0. Mechanical shock + water spray integrity: EN 50200 Annex E. System circuit integrity per installation system: DIN 4102-12, E30. Also complies with BS 5839:2002 test clause requirements.
Flame Retardancy & Reduced Flame Spread
Single vertical cable flame test: EN/IEC/BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1 (C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*. Bunched vertical cable flame spread reduction: EN/IEC/BS EN 60332-3-24 (cat. C); VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2 (C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4.
Halogen-Free, Low Smoke & Non-Toxic
Zero halogen: IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1; BS 6425-1*. Non-corrosive gas emission: IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2; BS 6425-2*. Minimum smoke emission: IEC/EN 61034-1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*. Non-toxic gas: NES 02-713; NF C 20-454.
BS 7629-1 / EN 50173 / IEC 61156
Designed per BS 7629-1, IEC 61156 and BS EN 50288 system requirements, compatible with all leading connection systems complying with EN 50173.
LSZH per BS 7652 §6.1 / BS 7655 §2.6
Outer sheath complies with BS 7652 §6.1 and BS 7655 §2.6 thermoplastic requirements, LSZH compound LTS3 class (SW2-SW4 type).
Need Fire-Resistant CAT3 FTP Data Cable?
Send us your required pair count, jacket color and applicable fire/smoke standards. Our team will review your specification and prepare a quotation.