Kexingyu E-Power Group
Home » Cables & Wires » Special/Industrial Cables » Fire-Resistant Cable » Mica Tape + XLPE/Silicone Insulated Screened Multi-Pair Instrumentation Cable (300/500V)

Special Wire and Cable > Fire-Resistant Cable

Mica Tape + XLPE/Silicone Insulated, Individual & Overall Screened Multi-Pair Instrumentation Cable (300/500V)

Designed, produced and tested as an emergency data transmission cable, this instrumentation cable ensures high-frequency signal transmission under fire conditions, commonly used for data and voice transmission during fire events.

Available with either mica tape + XLPE insulation or silicone rubber insulation, and in non-armoured or galvanized steel wire armoured (SWA) constructions, the cable features both individual pair screening and an overall screen for superior noise immunity in demanding instrumentation environments.

Key Features

FIR

Emergency Fire Data Transmission

Designed, produced and tested for high-frequency signal transmission during fire events, per IEC 60331-21 and BS 6387 CWZ.

2IN

Two Insulation Options

Choose mica tape + XLPE insulation (250°C short-circuit rating) or silicone rubber insulation (350°C short-circuit rating).

PSC

Individual + Overall Screen

Aluminum/polyester tape with tinned copper drain wire on both individual pairs and the overall cable for superior noise immunity.

ARM

Optional Steel Wire Armour

Non-armoured or SWA (steel wire armoured) construction available, with an additional LSZH layer on armoured versions.

LSZ

Low Smoke Zero Halogen

LSZH sheath per BS 7652 §6.1 / BS 7655 §2.6 LTS3 class, with low halogen and corrosive gas emission for occupied buildings.

DUL

Dual CE & UL Certification

Certified to both European CE and North American UL standards for global fire alarm and instrumentation project compliance.

OEM & ODM Capabilities

INS

Choice of Insulation Material

Select mica tape + XLPE (RE-2X series) or silicone rubber (RE-2G series) insulation based on your temperature and fire performance needs.

ARM

Armoured or Non-Armoured

Choose non-armoured construction or SWA (steel wire armoured) version with additional LSZH layer for mechanical protection.

PRS

Custom Pair Count & Size

Available in 2/5/10/20-pair configurations with 1.0/1.5/2.5mm² conductor cross-sections.

STD

Multi-Standard Compliance Support

Engineering support to align cable selection with country-specific fire, smoke and toxicity standards for your project.

LEN

Custom Length & Drum Packaging

Supplied in custom cut lengths and reel/drum packaging configurations to suit project logistics needs.

OEM

Private Labeling & Branding

OEM/ODM packaging, reel labeling and documentation support available for distributors and fire system contractors.

Technical Specifications

General Specifications
ConductorPlain annealed copper wire, stranded, per IEC(EN) 60228 class 2
Insulation Option 1Mica tape + XLPE (RE-2X series)
Insulation Option 2Silicone rubber (RE-2G series)
Pair TwistingDifferent lay lengths per pair to minimize interference; 4 cores per twisted-pair group
CablingPairs assembled together; groups of 8+ pairs bundled, then multiple bundles assembled together
Individual Pair ScreenAluminum/polyester tape with 0.5mm² tinned copper drain wire
Overall ScreenAluminum/polyester tape with 0.5mm² tinned copper drain wire
Inner Sheath (Armoured Version)Thermoplastic LSZH compound LTS3 class, per BS 7655 §6.1
Armour (SWA Version)Galvanized steel wire armour
Outer SheathThermoplastic per BS 7652 §6.1 / BS 7655 §2.6, LSZH compound LTS3 class (SW2-SW4 type)
Working Voltage300/500V
Dielectric Test2000V r.m.s. × 5 min (core-to-core)
Insulation Resistance≥1000MΩ×km at 20°C
Short-Circuit TemperatureXLPE: 250°C; Silicone Rubber: 350°C
Operating Temperature (Fixed)-30°C ~ +90°C
Installation Temperature-20°C ~ +50°C
Min. Bending Radius6 × OD (silicone rubber, non-armoured); 8 × OD (XLPE, non-armoured); 10 × OD (armoured)
CertificationDual certified: EU CE, North America UL
Specifications reflect standard construction across both insulation options and both armoured/non-armoured versions. Pair count and conductor size are configurable per project — see the dimensional data tables below.
Performance Snapshot
Working Voltage300/500V
Short-Circuit Temp.250–350°C
Fire RatingFE180 (PH30)
CertificationCE + UL
Fire-Resistant
PiMF Screened
XLPE / Silicone
Optional SWA
LSZH
CE + UL Certified
Non-Armoured Cable — Dimensional Data (RE-2X(St)H / RE-2G(St)H PiMF)
Nominal Cross-Section (mm²) No. of Pairs × Size Strands/Diameter (No./mm) Nominal Insulation Thickness (mm) Cable OD (mm) Nominal Weight (kg/km)
1.02 pairs7/0.430.615.2166
1.52 pairs7/0.530.717.0205
2.52 pairs7/0.670.819.2350
1.05 pairs7/0.430.617.5335
1.55 pairs7/0.530.721.5433
2.55 pairs7/0.670.824.0592
1.010 pairs7/0.430.622.5626
1.510 pairs7/0.530.728.0811
2.510 pairs7/0.670.831.51132
1.020 pairs7/0.430.630.51143
1.520 pairs7/0.530.738.01509
2.520 pairs7/0.670.842.52112
Armoured (SWA) Cable — Dimensional Data (RE-2X(St)HSWAH / RE-2G(St)HSWAH PiMF)
Nominal Cross-Section (mm²) No. of Pairs × Size Strands/Diameter (No./mm) Nominal Insulation Thickness (mm) Diameter Under Armour (mm) Armour Wire Diameter (mm) Cable OD (mm)
1.02 pairs7/0.430.615.20.9020.0
1.52 pairs7/0.530.717.01.2522.7
2.52 pairs7/0.670.819.21.2524.9
1.05 pairs7/0.430.617.51.2523.2
1.55 pairs7/0.530.721.51.6028.1
2.55 pairs7/0.670.824.01.6030.8
1.010 pairs7/0.430.622.51.6029.3
1.510 pairs7/0.530.728.01.6035.0
2.510 pairs7/0.670.831.52.0039.5
1.020 pairs7/0.430.630.52.0038.5
1.520 pairs7/0.530.738.02.0046.2
2.520 pairs7/0.670.842.52.5051.9
Nominal weight for the armoured (SWA) version was cut off in the original technical documentation and is not included above. Please contact us for exact armoured cable weight per size.

Construction & Configuration

Numbered diagram of fire-resistant instrumentation cable construction layers: conductor, insulation, individual screen, overall screen, optional armour, LSZH sheath
01

Conductor

Plain annealed copper wire, stranded, complying with IEC(EN) 60228 class 2.

02

Insulation (2 Options)

Mica tape + XLPE (RE-2X series, 250°C short-circuit rating) or silicone rubber (RE-2G series, 350°C short-circuit rating).

03

Individual + Overall Screen (PiMF)

Each pair individually screened with aluminum/polyester tape and a 0.5mm² tinned copper drain wire, plus an overall screen of the same construction.

04

Optional Armour (SWA)

Armoured versions add an inner LSZH sheath, galvanized steel wire armour, and an additional outer LSZH sheath layer.

05

Outer Sheath

LSZH thermoplastic sheath per BS 7652 §6.1 / BS 7655 §2.6 on all versions.

06

Pair & Size Configuration

Available in 2/5/10/20-pair configurations with 1.0/1.5/2.5mm² conductor cross-sections, per the dimensional data tables above.

Standards & Test Documentation

CIRCUIT INTEGRITY

Fire Circuit Integrity Standards (FE180)

IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814 (FE180); BS 8434-2 (120mins); BS 5839-1 Clause 26.2e; CEI 20-36/2-1; SS 229-1; NBN C 30-004 (cat. F3); NF C32-070-2.3 (CR1). Mechanical shock integrity: EN 50200 (PH120), CEI 20-36/4-0. Mechanical shock + water spray integrity: EN 50200 Annex E. System circuit integrity per installation system: DIN 4102-12, E30.

FLAME & FIRE PROPAGATION

Flame Retardancy & Reduced Flame Spread

Single vertical cable flame test: EN/IEC/BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1 (C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*. Bunched vertical cable flame spread reduction: EN/IEC/BS EN 60332-3-24 (cat. C); VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2 (C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4.

LOW SMOKE & TOXICITY

Halogen-Free, Low Smoke & Non-Toxic

Zero halogen: IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1; BS 6425-1*. Non-corrosive gas emission: IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2; BS 6425-2*. Minimum smoke emission: IEC/EN 61034-1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*. Non-toxic gas: NES 02-713; NF C 20-454.

CERTIFICATION

Dual CE & UL Certified

Certified to both European CE and North American UL standards, in addition to the full fire, smoke and toxicity performance suite listed above.

INSULATION OPTIONS

XLPE (250°C) or Silicone Rubber (350°C)

Choose the insulation type that matches your short-circuit temperature requirements — mica tape + XLPE or silicone rubber construction.

SHEATH MATERIAL

LSZH per BS 7652 §6.1 / BS 7655 §2.6

Outer sheath complies with BS 7652 §6.1 and BS 7655 §2.6 thermoplastic requirements, LSZH compound LTS3 class (SW2-SW4 type).

GET A QUOTE

Need Fire-Resistant Screened Instrumentation Cable?

Send us your required insulation type, pair count, and whether armoured protection is needed. Our team will review your specification and prepare a quotation.