FFX-CAT3FTPXP22FR Fire-Resistant CAT3 FTP Data Cable

Designed as a circuit-integrity fire alarm wiring cable compatible with all leading connection systems complying with EN 50173, this CAT3 FTP shielded data cable is engineered per IEC 61156 and BS EN 50288 system requirements.

Available in 1, 2 or 4-pair configurations with an overall aluminum/polyester tape screen and tinned copper drain wire, the cable continues transmitting data even when directly exposed to fire, while offering reliable data transmission and circuit integrity performance. It also complies with BS 5839:2002 test clause requirements.

Key Features

FIR

Circuit Integrity Under Fire

Continues transmitting data when directly exposed to fire, complying with IEC 60331-21, BS 6387 CWZ and BS 5839:2002 test requirements.

FTP

Overall Foil Screen

Aluminum/polyester tape overall screen with tinned copper drain wire provides EMC protection beyond unshielded UTP constructions.

LSZ

Low Smoke Zero Halogen

LSZH sheath per BS 7652 §6.1 / BS 7655 §2.6 LTS3 class, with low halogen and corrosive gas emission for occupied buildings.

EN5

EN 50173 Compatible

Compatible with all leading structured cabling connection systems complying with EN 50173, IEC 61156 and BS EN 50288.

INS

High Insulation Resistance

Insulation resistance ≥1000MΩ×km at 20°C, supporting reliable long-distance signal integrity.

OEM & ODM Capabilities

PRS

1/2/4-Pair Options

Available as FFX-CAT3FTP1P22FR, FFX-CAT3FTP2P22FR or FFX-CAT3FTP4P22FR to match your circuit count requirements.

CLR

Choice of Jacket Color

Available in red, white or black outer jacket to support circuit identification and fire alarm color-coding conventions.

STD

Multi-Standard Compliance Support

Engineering support to align cable selection with country-specific fire, smoke and toxicity standards for your project.

BND

Bundled Multi-Cable Configuration

Cables can be assembled into bundles of 8 pairs or more, and further grouped into larger multi-bundle assemblies for large installations.

LEN

Custom Length & Reel Packaging

Supplied in custom cut lengths and reel/coil packaging configurations to suit project logistics needs.

OEM

Private Labeling & Branding

OEM/ODM packaging, reel labeling and documentation support available for distributors and fire system contractors.

Technical Specifications

General Specifications
ConductorPlain annealed copper wire, stranded, per IEC(EN) 60228 class 2
InsulationPolyethylene with fire-resistant silicone rubber E12 class, per BS 7655 §1.1
Pair TwistingDifferent lay lengths per pair to minimize crosstalk; 4 cores per twisted-pair group
CablingPairs assembled together; groups of 8+ pairs bundled, then multiple bundles assembled together
Overall ScreenAluminum/polyester tape with tinned copper drain wire
Fire Barrier LayerNone
ArmourNone
Outer SheathThermoplastic per BS 7652 §6.1 / BS 7655 §2.6, LSZH compound LTS3 class (SW2-SW4 type)
Jacket ColorRed, white or black (customer choice)
Working Voltage60V
Design StandardBS 7629-1 / EN 50173
Insulation Resistance≥1000MΩ×km at 20°C
Short-Circuit Temperature50°C
Operating Temperature (Fixed)-5°C ~ +50°C
Installation Temperature-20°C ~ +90°C
Min. Bending Radius8 × OD
Specifications reflect standard construction. Pair count and jacket color are configurable per project — see the OEM & ODM section above and the dimensional/transmission data below.
Performance Snapshot
Working Voltage60V
Insulation Resistance≥1000MΩ×km
Min. Bend Radius8 × OD
Fire-Resistant
CAT3 FTP
LSZH
EN 50173 Compatible
Circuit Integrity
Transmission Characteristics
Frequency (MHz) NEXT (dB/100m) Min/Typ/Standard Insertion Loss – IL (dB/100m) Structural Return Loss – SRL (dB/100m) Min/Typ/Standard
143.0/48.0/41.02.613.0/16.0/12.0
434.0/38.0/32.05.613.0/16.0/12.0
829.0/33.0/26.08.513.0/16.0/12.0
1028.0/33.0/26.09.813.0/16.0/12.0
1625.0/30.0/23.013.111.0/14.0/10.0
Dimensional Data — 1/2/4-Pair Variants
Cable Code No. of Pairs Insulation Thickness (mm) Nominal Diameter (mm) Nominal Weight (kg/km)
FFX-CAT3FTP1P22FR10.256.848
FFX-CAT3FTP2P22FR20.258.197
FFX-CAT3FTP4P22FR40.2510.4122

Construction & Configuration

Numbered diagram of fire-resistant CAT3 FTP cable construction layers: conductor, silicone insulation, foil screen with drain wire, LSZH outer sheath
01

Conductor

Plain annealed copper wire, stranded, complying with IEC(EN) 60228 class 2.

02

Insulation & Pair Twisting

Fire-resistant silicone rubber E12 class insulated polyethylene, twisted with varying lay lengths per pair to minimize crosstalk.

03

Overall Screen

Aluminum/polyester tape overall screen with a tinned copper drain wire for EMC protection (FTP construction).

04

Fire Barrier & Armour

No dedicated fire barrier layer or armour — fire performance is achieved through insulation and sheath material selection.

05

Outer Sheath

LSZH thermoplastic sheath per BS 7652 §6.1 / BS 7655 §2.6, available in red, white or black.

06

Pair Count Configuration

Available in 1, 2 or 4-pair versions (FFX-CAT3FTP1P22FR / 2P22FR / 4P22FR), per the dimensional data table above.

Standards & Test Documentation

CIRCUIT INTEGRITY

Fire Circuit Integrity Standards

IEC 60331-21; BS 6387 CWZ; DIN VDE 0472-814 (FE180); BS 8434-2 (120mins); BS 5839-1 Clause 26.2e; CEI 20-36/2-1; SS 229-1; NBN C 30-004 (cat. F3); NF C32-070-2.3 (CR1). Mechanical shock integrity: EN 50200 (PH120), CEI 20-36/4-0. Mechanical shock + water spray integrity: EN 50200 Annex E. System circuit integrity per installation system: DIN 4102-12, E30. Also complies with BS 5839:2002 test clause requirements.

FLAME & FIRE PROPAGATION

Flame Retardancy & Reduced Flame Spread

Single vertical cable flame test: EN/IEC/BS EN 60332-1-2; VDE 0482-332-1; NBN C 30-004 (cat. F1); NF C32-070-2.1 (C2); CEI 20-35/1-2; EN 50265-2-1*; DIN VDE 0482-265-2-1*. Bunched vertical cable flame spread reduction: EN/IEC/BS EN 60332-3-24 (cat. C); VDE 0482-332-3; NBN C 30-004 (cat. F2); NF C32-070-2.2 (C1); CEI 20-22/3-4; EN 50266-2-4*; DIN VDE 0482-266-2-4.

LOW SMOKE & TOXICITY

Halogen-Free, Low Smoke & Non-Toxic

Zero halogen: IEC 60754-1; EN 50267-2-1; DIN VDE 0482-267-2-1; CEI 20-37/2-1; BS 6425-1*. Non-corrosive gas emission: IEC 60754-2; EN 50267-2-2; DIN VDE 0482-267-2-2; CEI 20-37/2-2; BS 6425-2*. Minimum smoke emission: IEC/EN 61034-1&2; DIN VDE 0482-1034-1&2; CEI 20-37/3-1&2; EN 50268-1&2*; BS 7622-1&2*. Non-toxic gas: NES 02-713; NF C 20-454.

SYSTEM COMPATIBILITY

BS 7629-1 / EN 50173 / IEC 61156

Designed per BS 7629-1, IEC 61156 and BS EN 50288 system requirements, compatible with all leading connection systems complying with EN 50173.

SHEATH MATERIAL

LSZH per BS 7652 §6.1 / BS 7655 §2.6

Outer sheath complies with BS 7652 §6.1 and BS 7655 §2.6 thermoplastic requirements, LSZH compound LTS3 class (SW2-SW4 type).